6wiring, 3 wiring examples – Pilz PDP67 F 8DI ION User Manual

Page 23

Advertising
background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-7

6.3

Wiring examples

6

Wiring

6.3.3

Example: Single-channel, failsafe input device, with test pulse

Example: Single-channel, failsafe input device, with test pulse

6-

Bsp 3: einkan fehlersich Sensor getaktet

Features:

Depending on the application area and its respective regulations, this
connection diagram is suitable in accordance with EN ISO 13849-1
up to PL d

and EN IEC 62061 up to SIL CL 2.

The input device must be approved for failsafe applications.

Test pulses can be used to check the inputs for short circuit to 24 V
and correct functionality. Short circuits that short out the input device
(cable from the test pulse to the input device and cable from the input
device to the input) will not be detected.

Please read the instructions provided with the input device.

Only input devices with N/C contacts can be tested.

Bsp: ACHTUNG Kurzschluss Bsp. 3

Bsp 3: einkan fehlersich Sensor getaktet_Zeichnung

CAUTION!
Short circuits between the cable to the input device and the 24 V
line or between cables to various input devices will not be
detected.
Avoid short circuits by

Appropriate wiring

Wiring in accordance with the requirements of IEC 61076-2-
101 and IEC 60204-1, clause 14.1.1 and 14.1.2

Advertising