CIRCUTOR CVM96 Series User Manual
Page 22
Advertising

----- Supply network analyzer CVM 96 ---------- ------- Page No. 21
5.8.- Clearing energy counters
On display we see "CLR ENER no" (Clear energy counters).
- "max": To select "YES" or "no"
- "
": To validate the choice and pass to the following SETUP option.
Display: If any of the energies is programmed (kWh, kvarhL or kvarhC), it is
displayed as follows:
kWh
max
MWh
min
Wh
Example : If the accumulated energy is 32.534,810 kWh, it will be displayed
as follows:
3 2
MWh
2 5 3 4
kWh
8 1 0
Wh
2534 kWh
max
32 MWh
min
810 Wh
Note : the energy counter range is limited at 999.999.999 Wh , that is, when the
value of 1 GWh is reached, the counter is reset to zero.
Advertising