----- Supply network analyzer CVM 96 ---------- ------- Page No. 41

b.- Reading digital outputs (relays) - Function 01 :

Inquiry

:

PP0100000008CRC (PP = peripheral No.)

Answer

:

PP0101XXCRC

Where XX (hexadecimal byte) translated to binary

b7 b6 b5 b4 b3 b2 b1 b0

bit b0 = relay 1 ( 1 = ON ; 0 = OFF)
bit b1 = relay 2 ( 1 = ON ; 0 = OFF)

c.- Write of digital outputs

This function is used to force the status of the CVM 96 digital outputs.

Output No.

Message

Answer

Relay 1
Relay 2

PP050000xx00 CRC
PP050001xx00 CRC

PP050000xx00 CRC
PP050001xx00 CRC

Where: PP peripheral No.

xx 00 Deactivate

FF Activate