CIRCUTOR CVM96 Series User Manual
Page 29

----- Supply network analyzer CVM 96 ---------- ------- Page No. 28
ALARM ACTIVATION: Alarms operation depend on the set values of MAXIMUM
and MINIMUM.
MIN +
MAX +
max > min
ON OFF ON
======
0 Min Max
MIN +
MAX +
max < min
OFF ON OFF
====
====
======
0 Max Min
MIN --
MAX +
ON OFF ON
=======
Min 0 Max
MIN +
MAX --
OFF ON OFF
=======
======
Max 0 Min
MIN --
MAX --
max > min
ON OFF ON
=====
Min Max 0
MIN --
MAX --
max < min
OFF ON OFF
=====
===========
Max Min 0
ON = alarm activated ----------> relay closed
OFF = alarm deactivated ------> relay open