Configuration and operation (cont.), Lcd models – Computronic Controls Sentinel 300P User Manual

Page 10

Advertising
background image

Sentinel 300P installation, operation & maintenance

ci0039 p10/12 issue 9 2015-09-04

LED indication

In normal operation, the four circuit board LEDs indicate
operating status: fault conditions, charge mode,
temperature compensation and AC supply:

LED operation

Status

Red

on

Fault condition (except AC supply &
battery connection errors).

flashing,
slow

AC supply not available
(DC connected).

flashing,
fast

Battery connection error.

off

No fault conditions.

Yellow

on

In Float mode.

flashing,
slow

In AutoBoost mode.

flashing,
fast

In AutoBoost extension mode / boost
decay.

off

Output off / output to nominal.

Blue

on

Temperature compensation active,
sensor connected.

flashing,
slow

Temperature compensation auto
disabled due to external fault.

flashing,
fast

Temperature compensation at absolute
limit, i.e. <

–10ºC or >+50ºC.

off

Temperature compensation disabled.

Green

on

AC supply available, charge output on.

flashing,
slow

AC supply available, charge output off.

flashing,
fast

Boost decay or battery missing
(if red LED is also on).

off

AC supply not available.

LCD Models

Enclosed models ESNTL300PCL and ESNTL300PCLM
include a backlit graphic LCD, three push-button controls
(Up, Down, Enter) and three additional indicating LEDs:

Green: CAN network status (CAN-enabled models only).

Lights continuously in normal CAN operation.

Yellow: charging mode, operation as yellow circuit board

LED.

Red: fault conditions, operation as red circuit board LED.

In normal charging mode, the LCD displays Sentinel and
battery status, e.g. operating mode, charge voltages and
currents, date/time, faults, etc.

In configuration menu modes, the LCD and push-buttons
can be used by the operator to view/edit operating
parameters and options (date/time, charge profiles, etc).

Normal charging: float and AutoBoost modes

At power-up, Sentinel
displays an initial message
that includes the unit
firmware version, followed

*******************
* SENTINEL 300P *
* V 3.0 *
*******************

by...

The default operating
screen, showing date, time,
battery volts, charge
current and charge mode.

20/05/10 10:23
VDC: 13.2 ADC: 8.5

FLOAT CHARGE

When Sentinel is in AutoBoost mode, the 4

th

line changes

to show the current boost stage, displaying (in sequence)
‘ramping to boost’, ‘boost extension’ and ‘boost decay’.

Fault messages

When a fault condition
occurs, an appropriate
message is shown on the
display 3

rd

line.

20/05/10 10:23
VDC: 13.2 ADC: 8.5
CHARGE FAIL
FLOAT CHARGE

Fault messages automatically clear from the display when
the fault condition clears. In the event of multiple faults,
the 3

rd

line displays the highest priority message, ranked

in the following order (highest priority first):

AC mains failure

DC connection error

Sensed connection error

Battery missing (detected during battery check routine)

Incorrect battery type (when configured with a 12V

charge profile, but the connected battery voltage is
above 16.1 V).

No

battery detected (when configured with an ‘auto’

charge profile, but the connected battery, or lack of
connection, is below 1.0V).

High battery voltage

Charge fail

Low battery voltage

Volt sense level fault

Configuration mode

The LCD and control keys can be used to view or change
configuration settings. The Sentinel 300P has three
configuration menus

, named ‘Settings’, ‘System’ and

‘CAN’. While the operator is viewing or editing these menu
settings, Sentinel continues normal charge operation, but
current charging status or fault information is not displayed
on the LCD.

Settings menu

This sequence of screens allows viewing (but not editing)
of several operating and device parameters.

To access the Settings
menu, press and hold the
Up and Down keys. The first
screen displayed is:

SETTINGS
FLOAT: XX.XVDC
BOOST: XX.XVDC
BOOST EXT: XXX MINS

Press Up or Down keys to
view more settings:

SETTINGS
LOW ALARM: XX.XVDC
HIGH ALARM: XX.XVDC
ALARM DELAY: XXX SEC

Press Up or Down keys to
view more settings:

SETTINGS
MODEL: XXXXXXXXX
SERIAL NO: XXXXXX FIRMWARE:
XXXXXXX

Press Up and Down to review the parameters again, or
press Enter to exit the Settings menu.

Configuration and Operation (cont.)

Advertising