Sentinel 300P installation, operation & maintenance

ci0039 p9/12 issue 9 2015-09-04

Configuration and Operation (cont.)

DIP switch configuration

WARNING: AC and DC connections must be isolated during DIP switch configuration. The correct battery type
and cell number must be configured correctly before charger power-up and battery connection. Incorrect
configuration may result in under or over charge of batteries, which may cause failure or damage to the batteries,
charger and connected equipment, and result in serious personal injury.

All Sentinel models include a 6 way DIP switch for configuration of battery type and cell number. The DIP switch is accessible
through a cut-out in the case rear:

Open frame SNTL models Enclosed ESNTL models

DIP

switch functions

:

1

– 4

Sets the charge profile (battery type and cell number) when

‘local’ mode is selected – see switch 6 below.

5

Sets whether the Sentinel charge profile is set in local or remote mode:
Local mode: charge profile set by DIP switches 1 to 4. The default setting is

‘Local, Auto’, where Sentinel auto-

matically selects 12 or 24V operation based on the battery voltage measured at power up

– see ‘operation’ below.

Remote mode: charge profile set by remote RS485 communication (e.g. SNTL300P-PCSUITE software), or (on
LCD models only) using display menu options. When remote mode is selected, the default charge profile is ‘Auto’.

6

Reserved use. Do not adjust from default (0/off/down) setting.

Nominal
voltage

Battery type

Profile name

DIP switch setting

(0 = off/down,

1 = on/up)

voltage/time settings

1 2 3 4 5 6 float

(VDC)

boost

(VDC)

boost

initiate

(VDC)

boost

time

(min)

low

alarm

(VDC)

high

alarm

(VDC)

DIP switches 1

– 4, local mode settings

12/24V

Auto
(12V or 24V wet lead acid)

AUTO DETECT

0 0 0 0 0 0 13.5/

27.0

14.1/

28.2

12.5/

25.0

360

12.0/

24.0

16.0/

32.0

12V

Wet (vented) lead acid, 6 cells

12V WET LA

0 0 0 1 0 0 13.5

14.1

12.5

360

12.0

16.0

Calcium Calcium, 6 cells

12V CA/CA

0 0 1 0 0 0 13.8

15.6

12.5

360

12.0

16.0

Lead acid hybrid Sb-Ca, 6 cells

12V LA HYBRID

0 0 1 1 0 0 13.5

14.7

12.5

360

12.0

16.0

VRLA, AGM, 6 cells

12V VRLA – AGM

0 1 0 0 0 0 13.5

14.4

12.5

360

12.0

16.0

VRLA, Gel, 6 cells

12V VRLA – GEL

0 1 0 1 0 0 13.5

13.8

12.5

360

12.0

16.0

NiCd, 10 cells

10 CELL NiCd

0 1 1 0 0 0 14.1

14.5

12.5

360

12.0

16.0

12V power supply

12V POWER SUPPLY 0 1 1 1 0 0 12.0

n/a

n/a

n/a

n/a

n/a

24V

NiCd, 18 cells

18 CELL NiCd

1 0 0 0 0 0 25.6

26.1

25.0

360

24.0

32.0

NiCd, 20 cells

20 CELL NiCd

1 0 0 1 0 0 28.2

29.0

25.0

360

24.0

32.0

Wet (vented) lead acid, 12 cells

24V WET LA

1 0 1 0 0 0 27.0

28.2

25.0

360

24.0

32.0

Calcium Calcium, 12 cells

24V CA/CA

1 0 1 1 0 0 27.6

31.2

25.0

360

24.0

32.0

Lead acid hybrid Sb-Ca, 12 cells 24V LA HYBRID

1 1 0 0 0 0 27.0

29.4

25.0

360

24.0

32.0

VRLA, AGM, 12 cells

24V VRLA - AGM

1 1 0 1 0 0 27.0

28.8

25.0

360

24.0

32.0

VRLA, Gel, 12 cells

24V VRLA - GEL

1 1 1 0 0 0 27.0

27.6

25.0

360

24.0

32.0

24V power supply

24V POWER SUPPLY 1 1 1 1 0 0 24.0

n/a

n/a

n/a

n/a

n/a

DIP switch 5: local / remote mode:
Local

x x x x 0 0 Local mode, profile set by switches 1-4

Remote

Auto Remote

x x x x 1 0 Remote mode, profile set by LCD or PC

software. Default charge profile: ‘Auto’.

DIP switch 6: reserved

x x x x x 0 Default setting, do not adjust.

Nominal
voltage

Battery type

Profile name

DIP switch setting

(0 = off/down, 1 =

on/up)

voltage/time settings

1

2

3

4

5

6

float

(VDC)

boost

(VDC)

boost

initiate

boost

time

low

alarm

high

alarm