Chapter 4 Parameters|

Revision Nov. 2008, VLE1, SW V1.03 4-25

00-07

Password Input

Unit: 1

Control

mode

VF

VFPG

SVC

FOCPG TQCPG FOCPM

Factory setting: 0

Settings

1 to 9998 and 10000 to 65535

Display

0~2 (times of wrong password)

The function of this parameter is to input the password that is set in Pr.00-08. Input the correct

password here to enable changing parameters. You are limited to a maximum of 3 attempts.

After 3 consecutive failed attempts, a fault code “Password Error” will show up to force the

user to restart the AC motor drive in order to try again to input the correct password.

When forgetting password, you can decode by setting 9999 and press button

PROG
DATA

twice.

Please note that all the settings will be set to factory setting.

00-08

Password Set

Unit: 1

Control

mode

VF

VFPG

SVC

FOCPG TQCPG FOCPM

Factory setting: 0

Settings

1 to 9998 and 10000 to 65535

Display

0

No password set or successful input in Pr. 00-07

1

Password has been set

To set a password to protect your parameter settings.

If the display shows 0, no password is set or password has been correctly entered in Pr.00-07.

All parameters can then be changed, including Pr.00-08.

The first time you can set a password directly. After successful setting of password the display

will show 1.

Be sure to record the password for later use.

To cancel the parameter lock, set the parameter to 0 after inputting correct password into Pr.

00-07.

The password consists of min. 2 digits and max. 5 digits.

How to make the password valid again after decoding by Pr.00-07:

Method 1: Re-input original password into Pr.00-08 (Or you can enter a new password if you

want to use a changed or new one).

Method 2: After rebooting, password function will be recovered.


Password Decode Flow Chart