Venting installation instructions – Desa T32N-a SERIES User Manual

Page 12

Advertising
background image

www.desatech.com

116646-01D

1

VENTING INSTallaTION INSTRUCTIONS

Continued

Vertical (V)

Required

Vertical (V) Vertical Pipe Horizontal (H)
*43

3

/

4

" min.

None

30" max.

53

3

/

4

" min.

1 ft.

48" max.

65

3

/

4

" min.

 ft.

60" max.

77

3

/

4

" min.

3 ft.

84" max.

89

3

/

4

" min.

4 ft.

0' max.

* Ground Floor Corner Venting

Figure 15 - Horizontal Termination Configuration for Corner Installation Using One

90° Elbow

Square
Termination

Wall
Firestop

Not to Exceed
(H) Limits

As Required
for (V), See
Chart for
Pipe Section
Required

45°
Elbow

90° Elbow

90°
Elbow

Square
Termination

Wall
Firestop

45°
Elbow

Not to Exceed
(H) Limits

1" Min.

CORNER INSTALLATION
Recommended Applications:

• Corner ground floor installation

• Ground floor installation where pipe vents horizontally through wall (over 12" horizontal pipe)

• Basement installation where one foot clearance from ground to termination is possible

SNORKEL TERMINATION INSTALLATION
Recommended Applications:

• Installations requiring a vertical rise on building

exterior

• Any installation using snorkel termination to

achieve one foot above ground

Snorkel
Termination

1" Min.

1" Min.

Adequate

Drainage

Snorkel

Termination

Snorkel

Termination

90° Elbow

1" Min.

Wall

Firestop

Snorkel terminations are available for installations

requiring a vertical rise on the exterior of the build-

ing. If installing snorkel termination below grade,

you must provide proper drainage to prevent water

from entering snorkel termination (see Figure 16).

Do not back fill around snorkel termination.

Figure 16 - Snorkel Termination Configurations for Below Ground Installation