Fireplace installation – Desa T32N-a SERIES User Manual

Page 21

Advertising
background image

www.desatech.com

116646-01D

1

Figure 32 - Gas Connection

CSA Design-Certified
Equipment Shutoff Valve with
1/8" NPT Tap*

3" Minimum

Approved
Flexible Gas
Line

Cap Pipe Nipple Tee Joint

Sediment Trap/Drip Leg

Natural - From
Gas Meter (5.5"
W.C. to 10.5"
W.C. Pressure)
Propane/LP
From External
Regulator (11"
W.C. to 14"
W.C. Pressure)

* The CSA design-certified equipment shutoff

valve may be supplied with the appliance or you

can purchase it from your retailer.

We recommend that you install a sediment trap/drip

leg in supply line as shown in Figure 32. Locate

sediment trap/drip leg where it is within reach for

cleaning. Install in piping system between fuel

supply and fireplace. Locate sediment trap/drip

leg where trapped matter is not likely to freeze. A

sediment trap traps moisture and contaminants. This

keeps them from going into fireplace gas controls. If

sediment trap/drip leg is not installed or is installed

wrong, fireplace may not run properly.

FIREplaCE

INSTallaTION

Continued

Figure 33 - Connecting Flexible Gas Line

to Millivolt Valve

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping

and connections, internal and

external to unit, for leaks after

installing or servicing. Correct

all leaks at once.

WARNING: Never use an open

flame to check for a leak. Apply

noncorrosive leak detection fluid

to all joints. Bubbles forming show

a leak. Correct all leaks at once.

pRESSURE TESTING GAS SUppLY
pIpING SYSTEM
Test pressures In Excess Of 1/2 pSIG
(3.5 kPa)

1. Disconnect fireplace and its individual equip-

ment shutoff valve from gas supply piping

system. Pressures in excess of 1/2 psig (3.5 kPa)

will damage fireplace gas regulator.

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas fireplace or opening main gas

valve located on or near gas meter for natural

gas fireplace or using compressed air.

4. Check all joints of gas supply piping system.

Apply noncorrosive leak detection fluid to all

joints. Bubbles forming show a leak. Correct

all leaks at once.

5. Reconnect fireplace and equipment shutoff

valve to gas supply. Check reconnected fittings

for leaks.

Flexible Gas Line
Do NOT Kink

Equipment
Shutoff
Valve

To Gas Supply
(Natural)

To External
Regulator
(Propane/LP)

Control Valve

CONNECTING FIREpLACE TO GAS
SUppLY

Installation Items Needed

• 5/16" hex socket wrench or nut-driver

• sealant (resistant to propane/LP gas, not pro-

vided)

1. Open lower louver door panel by gently

pulling forward.

2. Route flexible gas line (provided by installer)

from equipment shutoff valve to fireplace.

Route flexible gas supply line through one

of the access holes on side of fireplace.

3. Attach flexible gas line from gas supply

to control valve (see Figure 33).

4. Check all gas connections for leaks. See

Checking Gas Connections.