Elgar CW-M Series

M161570-01

3-11

3.5.1

S

INGLE

–P

HASE

S

UPPLY

C

ONNECTIONS

1. Remove the protective cover from the terminal block.

2. Route the cables through the strain relief device. Refer to Table 3

–2 for cable

recommendations.

3. Connect SAFETY Ground to the Ground stud located next to the INPUT

terminal block. For additional safety, include a loop between the Ground stud
and the strain relief device, as shown in Figure 3-6.

4. Connect shields, if any, to the GND connector of the INPUT terminal block.

5. Connect NEUTRAL, if available, to the NEUT connector.

6. Connect LINE to the LINE connector.

7. Reinstall the protective cover on the terminal block. Tighten the strain relief

device.

3.5.2

S

PLIT

–P

HASE

S

UPPLY

C

ONNECTIONS

120–0–120V

1. Remove the protective cover from the terminal block.

2. Route the cables through the strain relief device. Refer to Table 3

–2 for cable

recommendations.

3. Connect NEUT to 120V.

4. Connect LINE to the other 120V. Wiring across the full voltage will allow lower

line currents to be used.

5. Reinstall the protective cover on the terminal block. Tighten the strain relief

device.

3.5.3

T

HREE

–P

HASE

S

UPPLY

C

ONNECTIONS

1. Remove the protective cover from the terminal block.

2. Route the cables through the strain relief device. Refer to Table 3

–2 for cable

recommendations.

3. Connect one phase to LINE and NEUTRAL to NEUT. If NEUTRAL is not

available, connect LINE and NEUT across any of the phases.

4. Reinstall the protective cover on the terminal block. Tighten the strain relief

device.

Table 3

–2. Recommended Cables

CW Model

North American

International

CW 801M

18A/300V, 3x14 AWG
O.D.= 9.6 mm

16A/300V, 3x1.5 mm

2

O.D.= 8.0

–9.8 mm VDE

CW 1251M and CW 2501M

25A/300V, 3x12 AWG
O.D.= 11.3 mm

25A/300V, 3x25 mm

2

O.D.= 9.6

–12.0 mm VDE