Status screen #6 – Auto-Zone Control Systems Auto-Zone CV & CV-EX Systems Installation & Operation (Version 01C) User Manual

Page 59

Advertising
background image

Auto-Zone CV & CV-EX

Section 3

Programming

3-15

Status Screen #6













Note: If no alarm conditions exist, then line 3 will display the words No Alarms!

Line 4 - Mech Cooling ALARM

Mech Heating ALARM
This line remains blank if no alarm condition
exists.

These alarms are generated when the Supply
Temperature does not change more than five
degrees after a stage of heating or cooling has been
activated for 30 minutes.






CVAHU # 18 vl.xx

Zone Cooling ALARM

Line 2 - Zone Sensor O.K.

Bad Zone Sensor!
Zone Cooling ALARM
Zone Heating ALARM
The line will show Zone Sensor OK if none of the
above alarm conditions exist.

Line 3 - Binary Input ALARM

This line will remain blank if the contact has not
closed. This input is normally used for Dirty Filter
Alarms.

If no alarm conditions exist, then line 3 will display
the words No Alarms!

Advertising