Section 3

Auto-Zone CV & CV-EX

3-16

Programming

CV Controller Setpoints

Line 1 displays CVAHU Setpoints message for identification only.

Setpoint Screen #1





Setpoint Screen #2






CVAHU Setpoints

Occupied Setpoints

Cooling Setpt: 75°F

Heating Setpt: 72°F

The Occupied Heating and Cooling Setpoints are entered on
this screen. The Heating Setpoint should always be at least one
degree below the Cooling Setpoint, or the CVAHU will not
accept the new values.

Minimum

Default

Maximum

Cooling

Setpoint

50°F 75°F 90°F

Heating

Setpoint

50°F 72°F 90°F

CVAHU Setpoints

Unoccupied Setpoints

Cool Setup...: 10°F

Heat Setback.: -10°F

The Unoccupied Heating and Cooling Setup values are
entered on this screen. The Occupied Cooling Setpoint will be
increased by the Cooling Setup during Unoccupied Mode, and
the Heating Setpoint will be decreased by the Heating Setback.

Minimum

Default

Maximum

Cooling Setup

0°F

10°F

30°F

Heating Setback

0°F

-10°F

-30°F