Auto-Zone CV & CV-EX

Section 4

Start-Up and Troubleshooting

4-13

Note

: All temperature sensors must be Thermistor Type III which provides 77

°F @

10K Ohms Resistance.

Analog Output Description

Analog Output - This output is used to control the Outdoor Air Damper if you configure
the unit for Economizer control. The output voltage range is user-programmable to cover
all types of proportional actuators. 0 - 10 VDC, 2 - 10 VDC outputs are possible.

Relay Output Descriptions

Output #1 - Main Fan ON/OFF Control

Output #2 - Mechanical Heating / Cooling Stage #1

Output #3 - Mechanical Heating / Cooling Stage #2

Output #4 - Mechanical Heating / Cooling Stage #3

Output #5 - Mechanical Heating / Cooling Stage #4

Any combination of heating and cooling stages may be configured during setup as long as
the required number of outputs does not exceed four.

RS-485 Communications Connector

This connector provides the connection point for the Local Loop RS-485 communications
loop. The wiring consists of a twisted pair of wires with a shield.

T - RS485 (+) Communications terminal

SHLD
- Common return wire, this point is internally tied to GND on the

CV Controller.


R - RS485 (-)
Communications terminal