Extra room power heat duct instructions, Duct installation, Duct routing – Avalon Firestyles Extra Room Power Heat Duct User Manual

Page 3: Blower mounted in wall or ceiling

Advertising
background image

Extra Room Power Heat Duct Instructions

SKU 98500769

Page 3 of 11

12/2/13 - 17601067

© Travis Industries, Inc.

Duct Installation

Duct Routing

Determine the route for the heat duct using the illustration below as a guide.

Use 10” x 3-1/4” wall stack

(duct) when passing

through tight areas.

20’ Maximum

Length

Duct Adapter

(6” Round to 10” x 3-1/4” -

included with the power heat

vent kit)

Blower Box

0” Clearance to

Combustibles

Co-Axial Vent

(for intake air

and exhaust)

NOTE:
Air flow through the duct is affected by
length and number of bends. Keep the
length and number of bends to the minimum
to maximize performance.

When the duct penetrates the

fireplace enclosure vertically and the

top of the enclosure is within 36” of

the top of the fireplace, a firestop

spacer that maintains a 1/2”

clearance between all sides of the

duct and any combustible material

must be used.

1/2”

Blower Mounted in Wall or Ceiling

b

Attach the wall mounting

brackets to the blower box.

Mount the bracket to

these holes for 2 x 4 walls

Mount the bracket to

these holes for 2 x 6 walls

Cut a hole between wall

framing members for the

blower assembly.

a

5-1/4"

16"*

c

Slide the blower, with

wires, into the hole cut

in step "a". Attach

with four screws.

* This blower was designed for framing on 16" centers. Construct additional framing if needed. If the
blower is installed prior to the drywall only a 14" opening is required. If installed after the drywall is in
place, the drywall to the sides of the blower will need to be patched.