Basic Principles

11

BC2000


















Insulation testing











PE power contacts

inserted into the terminal without any force. The terminal closes
automatically when the pressure is released, holding the wire securely and
permanently.

The connection between the bus terminal controller and the bus terminals
is automatically realised by pushing the components together. The transfer
of the data and the supply voltage for the intelligent electronics in the bus
terminals is performed by the terminal bus. The supply of the field
electronics is performed through the power contacts. Plugging together the
power contacts creates a supply rail. Since some bus terminals (e.g.
analogue bus terminals or 4-channel digital bus terminals) are not looped
through these power contacts (or not completely) the bus terminal contact
assignments must be considered. The potential feed terminals interrupt the
power contacts, and represent the start of a new supply rail. The bus
terminal controller can also be made use of to feed the power contacts.

The power contact labelled “PE” can be used as a protective earth. For
safety reasons this contact mates first when plugging together, and can
ground short-circuit currents of up to 125 A. It should be noted that, for
reasons of electromagnetic compatibility, the PE contacts are
capacitatively coupled to the mounting rail. This can both lead to
misleading results and to damaging the terminal during insulation testing
(e.g. breakdown of the insulation from a 230 V power consuming device to
the PE conductor). The PE conductor to the bus terminal controller must be
disconnected for the insulation testing. In order to uncouple further feed
locations for the purposes of testing, the feed terminals can be pulled at
least 10 mm out from the connected group of other terminals. In that case,
the PE conductors do not have to be disconnected.

The “PE” power contact must not be used for other potentials.

Technical data

BC 2000

Number of bus terminals

64

Digital peripheral signals

256 inputs and outputs

Analogue peripheral signals 128 inputs and outputs
Peripheral bytes

512 inputs and 512 outputs

Fieldbus medium

Z1100 optical fibre

Plug connector

Z1000 for Z1100

Baud rate

2.5 Mbaud

Electrical power supply

24 V (- 15% / +20%) EN 61131

Input current

70 mA + (total terminal bus current)/4
500 mA max.

Power-on surge

2.5 x steady operating current

Terminal bus output current 1750 mA max.
Voltage

of

the

power

contact

24 V DC / AC

Power

contacts

current

drawn

10 A

Voltage stability

500 Veff (power contact / supply voltage)

Typical weight

170 g

Operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Relative humidity

95% without dew formation

Vibration/shock stability

according to IEC 68-2-6 / IEC 68-2-27

EMC immunity, burst / ESD

according to EN 61000-4-4 / EN 61000-4-2, limit values in accordance with
EN 50082-2

Installation location

arbitrary

Protection class

IP20