Cyc err wd plc – BECKHOFF BC2000 User Manual

Page 15

Advertising
background image

Basic Principles

BC2000

14

PLC LED

If the PLC LED lights, the program has started on the BC2000. The LED
flashes while a boot project is being created.


Diagnostic LEDs on the
BC2000

CYC

ERR

WD

PLC

The bus terminal controller interrogates the configuration of the bus
terminals after it has been switched on, then performs exchange of data
with the terminals. This means that the red I/O LED goes out after a fault-
free start-up, and the green I/O LED lights. The green I/O-LED lights with
the PLC timing on the bus terminal controller. If no program is running on
the BC2000, the pre-set cycle time for triggering the terminal bus is used.

CYC

ERR

WD

Meaning

Remedy

lit

off

lit

Telegrams are passing cyclically along
the ring
Inputs are read and outputs are set.

Everything is satisfactory

lit

off

lit

I/O-RUN flashes

The PLC cycle time that has been
set is too long > 100 ms

lit

off

off

The ring is functioning, but the bus
terminal

controller

is

not

being

addressed

Re-examine the control software
or the assignment list

blinking

off

off

The

controller

only

occasionally

accesses the bus. The outputs drop
away.

Re-examine the control software

off

lit

off

(Physical) bus fault, faulty telegrams are
circulating in the ring, e.g. optical fibre
damaged, previous module faulty, plug
not properly inserted

Check:
- whether the optical fibre cable is
inserted
- whether the optical fibre cable is
broken
- whether previous module is
ready for operation

off

blinking

off

Occasional CRC error (green I/O LED
lights)
Inputs are read; outputs are not
updated;

Optical fibre connection damaged

off

off

off

No operating voltage, serious fault, no
function

- Electrical power supply

Advertising