Preparing for operation and diagnostics – BECKHOFF BC2000 User Manual

Page 13

Advertising
background image

Basic Principles

BC2000

12

PLC data

BC 2000

Programmability

via

the

programming

interface

(TwinCAT

BC/TwinCAT)

or via optical fibre ring (TwinCAT)

Program memory

32 kbytes / 96 kbytes

Data memory

32 kbytes / 64 kbytes

Remanent flags

512 bytes

Runtime system

1 PLC task

PLC cycle time

approx. 3 ms for 1000 instructions (including terminal bus I/O cycle)

Programming languages

IL, LD, FBD, SFC, ST


Preparing for Operation and Diagnostics

After switching on, the bus terminal controller immediately checks the
connected configuration. Error-free start-up is signalled by extinction of the
red LED “I/O ERR“. If the “I/O ERR” LED blinks, an error in the area of the
terminals is indicated. The error code can be determined from the
frequency and number of blinks. This permits rapid rectification of the error.
There is a detailed description in the chapter on „The Diagnostic LEDs“.

The diagnostic LEDs

The bus terminal controller has two groups of LEDs for the display of
status. The upper group with four LEDs indicates the status of the
respective field bus. The significance of the “field bus status LEDs“ is
explained in the next sections of this manual - it conforms to conventional
field bus displays.

On the upper right hand side of the bus terminal controllers are two more
green LEDs that indicate the supply voltage. The left hand LED indicates
the 24 V supply of the bus terminal controller. The right hand LED signals
the supply to the power contacts.

Local errors

Two LEDs, the “I/O” LEDs, in the area below the field bus status LEDs
referred to above, serve to indicate the operating status of the bus
terminals and the connections to these terminals. The green LED lights up
in order to indicate fault-free operation. „Fault-free“ means that the
communication with the fieldbus system is also running. The red LED
flashes to indicate an error. The red LED blinks with two different
frequencies. The error is encoded in the blinks as follows:


Blink code

Fast blinking

Start of the error code

First slow sequence

Error type

Second slow sequence

Error location


Start of the error code

Error type

Error location

Advertising