Mounting and wiring

Fig. 6: Terminal points of KL3681

Terminal point No.

Comment

V

1

Terminal point for voltage measurement (internally connected with terminal point 5)

COM

2

Ground (internally connected with terminal point 6)

10 A

3

Terminal point for current measurement, 10 A range

Shield

4

Shield (internally connected with terminal point 8)

V

5

Terminal point for voltage measurement (internally connected with terminal point 1)

COM

6

Ground (internally connected with terminal point 2)

1 A

7

Terminal point for current measurement, 1 A range

Shield

8

Shield (internally connected with terminal point 4)

WARNING

Danger for persons through electric shock!

For voltages greater than 25 V

AC

 (42 V peak) or 60 V

DC

 the fuse opening must be covered

by an additional terminal or the EL9011 end terminal. Risk of electric shock!

Attention

10 A branch is not fuse­protected

The current branch for 10 A is not fuse­protected. The device may be damaged if the cur­
rent in the 10 A branch exceeds 10 A.

KL3681, KS3681

17

Version 2.0.0