Access from the user programm

5

Access from the user programm

5.1

Process image

Complex mapping

The following 9 bytes are transferred bi­directionally between KL3681 and control:

Byte offset (with­
out word align­
ment*)

Byte offset (with
word alignment*)

Format

Input data

Output data

0

0

Byte

Status byte (SB
[

}

 29])

Control byte (CB
[

}

 28])

1

2

Word

DataIN0

DataOUT0

3

4

Word

DataIN1

DataOUT1

5

6

Word

DataIN2

DataOUT2

7

8

Word

DataIN3

DataOUT3

*) Word alignment: The Bus Coupler places values on even byte addresses

Compact mapping (from firmware version 1C)

The following 8 bytes are transferred bi­directionally between KL3681 and control:

Byte offset (with and
without word align­
ment*)

Format

Input data

Output data

0

Word

DataIN0

DataOUT0

2

Word

DataIN1

DataOUT1

4

Word

DataIN2

DataOUT2

6

Word

DataIN3

DataOUT3

*) word alignment has no effect with compact mapping

5.2

Control and status byte

Process data mode

Control byte (in process data mode)

The control byte (CB) is located in the output image [

}

 28] and is transmitted from the controller to the

terminal.

Bit

CB.7

CB.6

CB.5

CB.4

CB.3

CB.2

CB.1 CB.0

Name RegAccess StartCalibration StartCalibration disAutorange

Voltage/Current DC/AC Range

KL3681, KS3681

28

Version 2.0.0