BECKHOFF KL3681 User Manual

Page 26

Advertising
background image

KS2000 Configuration software

Fig. 15: Settings via KS2000

Operating mode

Watchdog timer active (register page 0, register R32.2 [

}

 35])

Here you can deactivate the watchdog timer (default: active).

Frequency 60 Hz (register page 0, register R32.7 [

}

 35])

Here you can switch the terminal to a mains frequency of 60 Hz (default: 50 Hz).

User calibration active (register page 0, register R32.8 [

}

 35])

Here you can activate user calibration (default: inactive)

Filter enable (register page 0, register R32.11 [

}

 35])

Here you can disable the watchdog (default: enable).

Presentation

Here you can select the presentation format for the process data (default: scaled).

Options (register page 0, registers R32.15 to R32.12 [

}

 35])

• Left aligned*

• Right aligned

• Scaled

• Real

*) In left aligned presentation the extended measuring range is not available.

KL3681, KS3681

26

Version 2.0.0

Advertising
This manual is related to the following products: