Register page 1 – BECKHOFF KL3681 User Manual

Page 32

Advertising
background image

Access from the user programm

Register no.

Comment

Default value

R/W

Memory

R32 [

}

 35]

Feature register

0x2804

10244

dec

R/W

SEEPROM

R33 [

}

 36]

Zero Comp Interval

0x0000

0

dec

R/W

SEEPROM

R34

reserved

­

­

­

­

R35

reserved

­

­

­

­

R36 [

}

 36]

User scaling, measuring range 300 mV

DC

, offset

0x0000

0

dec

R/W

SEEPROM

R37 [

}

 36]

User scaling, measuring range 300 mV

DC

, gain

0x2000

8192

dec

R/W

SEEPROM

R38 [

}

 36]

User scaling, measuring range 3 V

DC

, offset

0x0000

0

dec

R/W

SEEPROM

R39 [

}

 36]

User scaling, measuring range 3 V

DC

, gain

0x2000

8192

dec

R/W

SEEPROM

R40 [

}

 36]

User scaling, measuring range 30 V

DC

, offset

0x0000

0

dec

R/W

SEEPROM

R41 [

}

 36]

User scaling, measuring range 30 V

DC

, gain

0x2000

8192

dec

R/W

SEEPROM

R42 [

}

 36]

User scaling, measuring range 300 V

DC

, offset

0x0000

0

dec

R/W

SEEPROM

R43 [

}

 36]

User scaling, measuring range 300 V

DC

, gain

0x2000

8192

dec

R/W

SEEPROM

R44 [

}

 36]

User scaling, measuring range 300 mV

AC

, offset

0x0000

0

dec

R/W

SEEPROM

R45 [

}

 36]

User scaling, measuring range 300 mV

AC

, gain

0x2000

8192

dec

R/W

SEEPROM

R46 [

}

 36]

User scaling, measuring range 3 V

AC

, offset

0x0000

0

dec

R/W

SEEPROM

R47 [

}

 36]

User scaling, measuring range 3 V

AC

, gain

0x2000

8192

dec

R/W

SEEPROM

R48 [

}

 36]

User scaling, measuring range 30 V

AC

, offset

0x0000

0

dec

R/W

SEEPROM

R49 [

}

 36]

User scaling, measuring range 30 V

AC

, gain

0x2000

8192

dec

R/W

SEEPROM

R50 [

}

 37]

User scaling, measuring range 300 V

AC

, offset

0x0000

0

dec

R/W

SEEPROM

R51 [

}

 37]

User scaling, measuring range 300 V

AC

, gain

0x2000

8192

dec

R/W

SEEPROM

R52 [

}

 37]

User scaling, measuring range 100 mA

DC

, offset

0x0000

0

dec

R/W

SEEPROM

R53 [

}

 37]

User scaling, measuring range 100 mA

DC

, gain

0x2000

8192

dec

R/W

SEEPROM

R54 [

}

 37]

User scaling, measuring range 1 A

DC

, offset

0x0000

0

dec

R/W

SEEPROM

R55 [

}

 37]

User scaling, measuring range 1 A

DC

, gain

0x2000

8192

dec

R/W

SEEPROM

R56 [

}

 37]

User scaling, measuring range 10 A

DC

, offset

0x0000

0

dec

R/W

SEEPROM

R57 [

}

 37]

User scaling, measuring range 10 A

DC

, gain

0x2000

8192

dec

R/W

SEEPROM

R58 [

}

 37]

User scaling, measuring range 100 mA

AC

, offset

0x0000

0

dec

R/W

SEEPROM

R59 [

}

 37]

User scaling, measuring range 100 mA

AC

, gain

0x2000

8192

dec

R/W

SEEPROM

R60 [

}

 37]

User scaling, measuring range 1 A

AC

, offset

0x0000

0

dec

R/W

SEEPROM

R61 [

}

 37]

User scaling, measuring range 1 A

AC

, gain

0x2000

8192

dec

R/W

SEEPROM

R62 [

}

 37]

User scaling, measuring range 10 A

AC

, offset

0x0000

0

dec

R/W

SEEPROM

R63 [

}

 37]

User scaling, measuring range 10 A

AC

, gain

0x2000

8192

dec

R/W

SEEPROM

Register page 1

These registers are used for calibration of the KL3681 (access selectable via register R4 [

}

 33]).

Register no.

Comment

Default value

R/W

Memory

R32 [

}

 38]

Internal calibration data

R

SEEPROM

...

...

...

...

R35 [

}

 38]

Internal calibration data

R

SEEPROM

R36 [

}

 38]

Manufacturer calibration

R

SEEPROM

...

...

...

...

R63 [

}

 38]

Manufacturer calibration

R

SEEPROM

KL3681, KS3681

32

Version 2.0.0

Advertising
This manual is related to the following products: