Status byte (in process data mode) – BECKHOFF KL3681 User Manual

Page 29

Advertising
background image

Access from the user programm

Bit

Name

Description

CB.7

RegAccess

0

bin

Register communication off (process data mode)

CB.6

R/W

0

bin

Read access

1

bin

Write access

CB.5

StartCalibration

1

bin

initiates an automatic correction of the internal measuring range
(only if register R33 = 4)

CB.4

disAutorange

0

bin

auto range enabled

1

bin

auto range disabled

CB.3

Voltage/Current

0

bin

Voltage

1

bin

Current

CB.2

DC/AC

0

bin

DC

1

bin

AC

CB.1, CB.0 Range

Measuring range (see also CB.2)

00

bin

3 V or 1 A

01

bin

30 V or 10 A

10

bin

300 V

11

bin

300 mV or 100 mA

Status byte (in process data mode)

The status byte (SB) is located in the input image [

}

 28] and is transmitted from terminal to the controller.

Bit

SB.7

SB.6

SB.5 SB.4

SB.3

SB.2

SB.1

SB.0

Name RegAccess Error

­

noAutorange data Invalid

extended range overrange

underrange

Bit

Name

Description

SB.7

RegAccess

0

bin

Acknowledge for process data mode

SB.6

Error

1

bin

measuring range exceeded, over or under range, the error LED
shines or converting error or invalid measuring range

SB.5

reserved

0

bin

reserved

SB.4

­

0

bin

auto range is enabled

1

bin

auto range is disabled

SB.3

data invalid

1

bin

invalidprocess data, e.g. invalid value, e.g. filter latency, start up

SB.2

extended range*

1

bin

The extended measuring range (~10% of upper range value) is
used (hysteresis area of auto range functionality).

SB.1

overrange

1

bin

Exceeding of the electrical measuring range

SB.0

underrange

1

bin

Undershooting of the electrical measuring range at DC mode
(not displayed in AC mode

*) The extended range is only available for the measuring ranges 300 mV, 3 V, 30 V and 100 mA.

Register communication

Control byte (at register communication)

The control byte (CB) is located in the output image [

}

 28] and is transmitted from the controller to the

terminal.

Bit

CB.7

CB.6

CB.5

CB.4

CB.3

CB.2

CB.1

CB.0

Name

RegAccess

R/W

Register no.

KL3681, KS3681

29

Version 2.0.0

Advertising