Analog Input Channel Object

27

IPxxxx-B520

Semantics

Status

The Status of an Analog Input Channel indicates the following conditions:

Value

Description

0

OK, no failure

1

internal IO Error
Over range
Under range
Diagnostics (depends on IPxxxx, see manual)
Idle Mode


Register 0 – 63

Within the response of a Get_Attribute_Single Service to the „Register
Data“ Attribute the status of the internal reading and the registers data is
returned by the IPxxxx. The meaning of the registers data is described in
the IPxxxx manual.
Within the response of a Set_Attribute_Single Service to the „Register
Data“ Attribute the status of the internal reading is returned by the coupler.


Get_Attribute Response

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Status (Low Byte)

1

Status (High Byte) : 0 = OK, >0 = Error

2

Register data (Low Byte)

3

Register data (High Byte)


Set_Attribute Request

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Register data (Low Byte)

1

Register data (High Byte)

2

Not used

3

Not used


Set_Attribute Responset

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Status (Low Byte)

1

Status (High Byte) : 0 = OK, >0 = Error




Common Services

Service Code

Service Name

Description

14

(0Ehex)

Get_Attribute_Single

Returns the contents of the specified
attribute

16

(10hex)

Set_Attribute_Single

Modifies an attribute Value