2 fieldbus / devicenet leds, 3 devicenet node address switches – BECKHOFF IPxxxx-B520 User Manual

Page 35

Advertising
background image

Indicators and Switches

IPxxxx-B520

32

10.2 Fieldbus / DeviceNet LEDs



DeviceNet Status LED

The red/green LED pair provides information about the device and com-
munication status of the IPxxxx-B520. The LEDs acts as the bi-color com-
bined Module/Network Status LED defined in the DeviceNet Specification.

The LED Pair is located next to the configuration interface for adjustment of
the DeviceNet address (MacId)





States of Module / Status
LED

LED State

Description

Green Flashing

Boot Up OK, Device has executed Duplicate MacId Check and
is ON-Line. The IPxxxx-B520 is not allocated by a Master /
Scanner, no Data Exchange with a Master / Scanner

Green ON

No Error, IPxxxx-B520 is allocated by a Master / Scanner, Data
Exchange (Explicit or IO) with Master / Scanner is OK

Green OFF

- Bus Sense Error (24V DeviceNet Voltage in not available)
(all LEDs off, including IO-Run, IO-Error LEDs)
- No BaudRate, IPxxxx-B520 is not able to detect BaudRate
(IO-Run, IO-Error LEDs On)

Red Flashing

Time Out, IO-Connection has timed out

Red ON

- Duplicate MacId Fault, check for same Address in Network
- Bus-Off, check cabling, check bus termination, check bus
length
- Receive/Transmit Overrun, reduce IO-Cycle Time / Interscan
delay at Master / Scanner

Red OFF

- Bus Sense Error (24V DeviceNet Voltage in not available)
(all LEDs off, including IO-Run, IO-Error LEDs)
- No BaudRate, IPxxxx-B520 is not able to detect BaudRate
(IO-Run, IO-Error LEDs On)



10.3 DeviceNet Node Address Switches





Node Address Switches

The Node Address Switches consist of two, ten position rotary switches
within the Configuration Interface of the IPxxxx-B520



Node Address Switches

Node Address Switch

Node Address

Description

0 - 63

Node Address from Switches is valid, not programmable

> 63

Node Address is programmable by Master / Scanner

Advertising