Fieldpiece STA2 - In Duct Hot-wire Anemometer User Manual

Fieldpiece, In-duct hot wire anemometer, In- duct hot wire anemometer

Advertising
background image

01

03

06

02

05

04

07

09

12

08

11

10

Quick Start

1. Power on your STA2 by holding the

ON/OFF button for 1 second. There is

a 5 second count down as the meter

warms up.

2. Use the arrow buttons to cycle the

display between air velocity, volu-

metric flow (CFM) and temperature.

3. Press the DUCT button to enter a

duct size.

4. Press and hold the HOLD (Average)

button to enter "Record Mode."

Record flow, velocity and tempera-

ture values, over time or at specific

points. Then average the recorded

values.

Certifications

C-Tick (N22675)

CE

WEEE

RoHS Compliant

Description

Your STA2 is a portable, hand held,

hot wire anemometer, designed for

the HVAC/R technician.

The compact probe tip makes

directly measuring air velocity a

breeze. The 38"(96cm) telescoping

probe with laser etched ruling and

flattened edges allows you to locate

proper measurement points within a

duct and ensures that your probe is

properly aligned.

The STA2 calculates air flow

(CFM) based off your inputs of duct

dimensions or free area, making

for quick and accurate readings, no

matter the duct size or shape.

Use either of the averaging methods

in Record Mode to counter turbulent

spikes in air velocity.

The dual display with a bright

backlight, and rugged rubber boot

with probe clips, make sure the STA2

is ready for any job.

Display

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Battery Life

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Auto Power Off Enabled

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Volumetric Flow

(cubic feet/minute)

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Volumetric Flow

(liters/second)

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Volumetric Flow

(cubic meters/hour)

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Velocity (feet/minute)

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Velocity (meters/second)

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Velocity (kilometers/hour)

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Velocity (miles/hour)

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Temperature (Fahrenheit)

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Temperature (Celsius)

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Length (inches)

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Length (centimeters)

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Length (feet)

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Length (meters)

Fieldpiece

In- Duct Hot Wire

Anemometer

OPERATOR'S

MANUAL

Model STA2

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Point Recording

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Time Recording

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Average Display

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Hold Display

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Maximum Display

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Minimum Display

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Free Area Input

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Duct Shapes

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Dimension Input

(diameter, height, width)

Controls

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Hold 1 second to toggle power on/off.

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Toggle Backlight. (Hold while powering

your STA2 on to disable APO.)

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Toggle display Hold (displays

average of recorded values

while in record mode).

Hold for 2 seconds or longer

to enter/exit record mode.

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Scroll up or down. Cycles displayed

measurement parameters (CFM, Velocity,

and Temp.)

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Press for duct setup.

Hold for 2 seconds for Units setup.

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Confirm Selection.

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

Displays Maximum or Minimum

values. Hold for 1 second to exit

and clear stored values.

Functions

Backlight

1. Press the backlight button to toggle the backlight

on/off at any time during the STA2's use.

Note: The backlight will automatically shut off after 1

minute to conserve battery life.

Hold

1. The HOLD button toggles the Hold Function on/off.

The Hold function will pause the measured values

on the upper and lower displays until cancelled.

2. Pressing the HOLD button for longer than 2 seconds

will take the STA2 into "Record Mode." (Please see

the Record Mode section for more information.)

Maximum/Minimum

1. Pressing the MAX/MIN button activates the Max-

Min function, holding the maximum and minimum

values measured until cleared.

2. Once the Max-Min function has been enabled,

pressing MAX/MIN cycles between displaying

maximum (MAX), minimum (MIN) and real time

values (MAX MIN).

Clear Data

1. Press and hold the MAX/MIN button for 2 seconds

to CLEAR DATA, this erases all stored data points

and resets the Record Mode counter to zero.

Display Scrolling

1. At any point during operation the arrow keys

may be used to change the display(s) on your

STA2 to show velocity, flow and temperature

measurements.

Duct Setup

1. Enables the STA2 to calculate volumetric flow

based on user entered information specific to the

equipment being worked on. Pressing the DUCT

button will lead you through the duct setup. (See

the "Set up your STA2" section for detailed use of

this function.)

Units Setup

1. To enter the Units setup mode hold down the DUCT

button for 2 seconds.

2. Use the Arrow and ENTER buttons to select air

velocity, flow, temperature and length units.

Note: Length units will also be used as area units for

Free Area inputs during Duct setup.

3. Once all units are selected you will be returned to

the main display screen.

Record Mode

Record Mode allows you to find the Average,

Maximum and Minimum of recorded

measurements taken over a length of time, or in

different positions.

1. Enter the Record Mode and select either time

or point recording. Time recording

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

will be

continuous, a point recording

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

will only record

at entered points. Use the Arrow buttons to choose

between time and point recording and press ENTER

to lock in your selection.

2. a.)Time Recording: Use the ENTER button to start

and pause recording. The lower display shows the

total time recorded.

b.) Point Recording: Press the ENTER button to

take a measurement at a specific point. The lower

display shows the total number of measurements

recorded.

3. Press the AVERAGE button to display the

average of recorded values. Press the MAX/MIN

button to display the maximum and minimum

measurements taken. These functions can be used

while still recording.

Note: Average replaces Hold while in Record Mode.

What is Free Area?

How Do I Get It?

Free Area is the total area through

which air can flow on either a supply

outlet or a return grille. Free area

is also sometimes referred to as

"effective area" or "see through area."

If there is no grille or restriction on

the area through which air is flowing

then the free area is equal to the actual

area. This would be the case if you

were measuring air flow in the middle

of a duct, or if you were to remove the

grille from a supply or return.

If you are measuring airflow where

there is a restriction present, then the

free area is the total area minus the

area covered by the fins or grating.

Free Area is published by grille

manufacturers and is the most

accurate representation of the Free

Area of a duct. Use manufacturer's

data whenever available.

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

How to Measure

Accurate Airflow

Find a Suitable Location

for a Traverse

1. The cross sectional area at, before, and after the

traverse location should be either rectangular

or round.

2. Make sure you have sufficient access around

the traverse location so that the duct may be

traversed at multiple angles.

3. The traverse location should be chosen so as to

minimize the effects of leaks in the portion of

the system between the fan and the traverse

location.

4. The traverse location should be located far

enough downstream of the fan to allow the

airflow to come to a uniform distribution.

To determine an effective length, assume a

minimum of 2.5 duct diameters for 2500ft/

min or less and add 1 duct diameter for each

additional 1000ft/min measured. (For a

rectangular duct the equivalent diameter can

be calculated as D=√(4hw/π) where “h” is the

height of the duct and “w” is the width.)

5. Locations directly downstream from

obstructions, bends or sudden changes in the

duct are not good locations for a traverse.

Set Up Your STA2

Press the DUCT button to enter Duct setup mode and

choose to input either duct dimensions or Free Area.

1. Duct dimensions: Use this option if measuring

in a duct or at an obstruction-free Supply/Return.

2. Use the arrow and ENTER buttons to select the

Duct dimensions icon.

3. Use the arrow and ENTER buttons to select the

shape of the Duct.

4. Use the arrow and ENTER buttons to enter either

the Height (H=) and Width (W=) of the duct

(for rectangular ducts) or the Diameter (D=) (for

round ducts).

1. Free Area: Use this option if measuring at a

Supply/Return with an obstruction such as a

grille and the free area is known.

2. Use the arrow and ENTER buttons to select the

Free Area icon.

3. Use the arrow and ENTER buttons to enter the

manufacturer specified Free Area.

After the appropriate information is input you will be

returned to the main display screen.

When you are ready to execute the traverse you will

want to put the STA2 into RECORD mode and select

time recording. Use the ENTER button to start and stop

recording at each of the points along your traverse. How

long you record at each point depends on how much

variance you see while measuring.

Continued on reverse...

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF