11.3 PMV D20 symptoms and solutions

Failure

Probable Cause

Corrective action

No LED is flashing.

Current source below 3,6 mA .

Verify current source
supplies at least 3,6 mA.

Incorrect wiring polarity.

Check wiring for correct
polarity.

Valve position reading

Stem position sensor mounting

Reposition sensor.

is not what is expected. is off 180 degrees.

D20 not calibrated.

Calibrate D20.

Tight shutoff MPC (Minimum

No action.

position cutoff) is active.

D20 goes in wrong

Change direction

direction.

(Section 9.4).

D20 is oscillating.

Decrese gain (Section 9.6).

D20 is responding slow.

Increse gain (Section 9.6).