11.3 PMV D20 symptoms and solutions
Failure
Probable Cause
Corrective action
No LED is flashing.
Current source below 3,6 mA .
Verify current source
supplies at least 3,6 mA.
Incorrect wiring polarity.
Check wiring for correct
polarity.
Valve position reading
Stem position sensor mounting
Reposition sensor.
is not what is expected. is off 180 degrees.
D20 not calibrated.
Calibrate D20.
Tight shutoff MPC (Minimum
No action.
position cutoff) is active.
D20 goes in wrong
Change direction
direction.
(Section 9.4).
D20 is oscillating.
Decrese gain (Section 9.6).
D20 is responding slow.
Increse gain (Section 9.6).