Wiring

Bus cable

Note that screened multi-core twisted-pair control cable is required as bus line, e.g.
UNITRONIC

®

BUS CAN 2x 2 x...mm² or RE - 2YCYV-fl 2x 2 x...mm².

The baud rate (data transfer rate) dictates the cable length between the bus nodes, and
the conductor size dictates the total power consumption of the sensor.

The baud rate is set via code switches

(S8 to S10). Default factory setting of control

unit LRR 1-40: baud rate 250 kbit /s (cable length 125 m).
For longer cable lengths reduce baud rate accordingly. Make sure that all bus nodes
feature the same settings.

UNITRONIC® is a registered trademark of LAPP Kabelwerke GmbH, Stuttgart.

S 8

S 9

S 10

Baud rate

Cable length

N umber of pairs and

conductor size [mm ²]

OFF

ON

OFF

250

125 m

2 x2 x0.34

Factory setting

ON

ON

OFF

125 kBits/s

250 m

2x2 x0.5

OFF

OFF

ON

100 kBits/s

335 m

2 x2 x0.75

ON

OFF

ON

50 kBits/s

500 m

available on demand (depends

on bus configuration)

OFF

ON

ON

20 kBits/s

1000 m

ON

ON

ON

10 kBits/s

1000 m