Action against high frequency interference, System faults, Fig. 7 – Flowserve LRR1-40 TDS Control Unit User Manual

Page 30

Advertising
background image

30

System Faults

– co ntinued –

Action against high frequency interference

Due to the digital signal evaluation we recommend the following measures for
interference suppression in installations susceptible to electromagnetic interference
(e.g. interference caused by phase asynchronous switching operations):

H. F. Interference suppression of voltage supply

Install ferrite ring just before the control equipment. Loop supply lines L and N as often
as possible (5-10 times) through the ring. Several control units that are located next to
each other can also be fed by this supply line.

L

Fig. 7

Ferrite ring

N

230V

Control unit

Control unit