Table Node ID
In a CAN bus system a maximum of 123 nodes (devices) can be administered. Each
node has its own address (node ID). This address can be set via a 10-pole code switch
.
(Factory setting) (Example)
( Factory setting 250 kBit /s )
Change factory setting
Use operating device URB or SPECTOR
control
to configure, parameterize, operate and
show the control parameters.
Node ID
50
Node ID
76
S1
OFF
1
S1
OFF
1
S2
ON
2
S2
OFF
2
S3
OFF
4
S3
ON
4
S4
OFF
8
S4
ON
8
S5
ON
16
S5
OFF
16
S6
ON
32
S6
OFF
32
S7
OFF
64
S7
ON
64
S8
S9
S0
Baud rate
Cable length
OFF
OFF
OFF
1000 kBit/ s
25 m
ON
OFF
OFF
500 kBit/s
100 m
OFF
ON
OFF
250 kBit/s
250 m
ON
ON
OFF
125 kBit/s
500 m
OFF
OFF
ON
100 kBit/s
670 m
ON
OFF
ON
50 kBit/s
1000 m
OFF
ON
ON
20 kBit/s
1000 m
ON
ON
ON
10 kBit/s
1000 m
D
ON
1 2 3
5
4
6 7 8 9 10
D
ON
1 2 3
5
4
6 7 8 910
D