Table node id, Change factory setting, Table node id change factory setting – Flowserve LRR1-40 TDS Control Unit User Manual

Page 34: Annex

Advertising
background image

34

Annex

– contin ued –

Table Node ID

In a CAN bus system a maximum of 123 nodes (devices) can be administered. Each
node has its own address (node ID). This address can be set via a 10-pole code switch

.

(Factory setting) (Example)

( Factory setting 250 kBit /s )

Change factory setting

Use operating device URB or SPECTOR

control

to configure, parameterize, operate and

show the control parameters.

Node ID

50

Node ID

76

S1

OFF

1

S1

OFF

1

S2

ON

2

S2

OFF

2

S3

OFF

4

S3

ON

4

S4

OFF

8

S4

ON

8

S5

ON

16

S5

OFF

16

S6

ON

32

S6

OFF

32

S7

OFF

64

S7

ON

64

S8

S9

S0

Baud rate

Cable length

OFF

OFF

OFF

1000 kBit/ s

25 m

ON

OFF

OFF

500 kBit/s

100 m

OFF

ON

OFF

250 kBit/s

250 m

ON

ON

OFF

125 kBit/s

500 m

OFF

OFF

ON

100 kBit/s

670 m

ON

OFF

ON

50 kBit/s

1000 m

OFF

ON

ON

20 kBit/s

1000 m

ON

ON

ON

10 kBit/s

1000 m

D

ON

1 2 3

5

4

6 7 8 9 10

D

ON

1 2 3

5

4

6 7 8 910

D