Max limit / min limit, Operation – Flowserve LRR1-40 TDS Control Unit User Manual

Page 24

Advertising
background image

24

Operation

– co ntinu ed –

MAX limit / MIN limit

Only applicable if:

Relay contact 1 (feedback LED 1) works as switching output for MAX limit

Relay contact 4 (feedback LED 4) works as switching output for MIN limit

LED 1 lights up once the set MAX limit is reached.
Relay contact 1 opens (safety circuit).

LED 1 goes out once the value falls below its limit.
Relay contact 1 closed.

LED 4 lights up once the set MIN limit is reached.
Relay contact 4 opens.

LED 4 goes out once the value exceeds its limit.
Relay contact 4 closed.

MAX limit / MIN limit = Automatic intermittent boiler blow down

Only applicable if:

Relay contact 1 (feedback LED 1) works as switching output for MAX limit and MIN limit

Relay contact 4 (feedback LED 4) works as switching output for automatic intermittent
boiler blowdown

LED 1 lights up once the set MAX or MIN limit is
reached. Relay contact 1 opens (safety circuit).

LED 1 is not lit if the actual value is between the MIN
and MAX limit. Relay contact 1 closed.

LED 4 is lit during intermittent blowdown and relay
contact 4 is closed. The intermittent blowdown valve
opens.

LED 4 is not illuminated during the time between
intermittent blowdown. Relay contact 4 is open, the intermittent blowdown valve is closed.

Test

Test

Test

Test

Note

The MIN limit is activated approx. 60 seconds after the mains voltage has
been applied. During this time LED 1 or - depending on the setting - LED 4
is flashing rapidly.

Advertising