Status diagnostics and troubleshooting

Displaying status
codes

The inverter performs a system self diagnosis that automatically detects many faults that
may occur and shows them on the display. This means you are promptly made aware of
malfunctions in the inverter and the photovoltaic system, or of any installation or operating
faults.

If the system self diagnosis has detected a specific fault, the associated status code will be
shown on the display.

Total failure of the
display

If the display fails to come on some time after sunrise:
-

Check the AC voltage ON the inverter connections:
the AC voltage must be 230 V (+ 10 % / - 5 %)*.

*

The mains voltage tolerance depends on the country setup

Class 1 status
codes

Class 1 status codes generally only arise momentarily and are caused by the public grid.

The initial response of the inverter in this case is to disconnect itself from the grid. The grid
is subsequently checked for the stipulated monitoring period. If no further problem has
been detected by the end of this period, then the inverter will resume feeding energy into
the grid.

The GPIS SoftStart function is activated according to the country setup:
after cutting out due to an AC error, the output power of the inverter is continuously in-
creased by 10% every minute in line with the VDE-AR-N 4105 guideline.

IMPORTANT! Status codes may sometimes appear briefly as a result of the inverter's con-
trol response. If the inverter then continues working with no sign of any problem, this
means that there was no fault.

Code

Description

Behaviour

Remedy

102

AC voltage too high

Following careful testing and
when the grid conditions are
within the permissible range
again, the inverter will resume
feeding energy into the grid.

Check grid connections:
If this status code keeps recur-
ring, contact your system engi-
neer

103

AC voltage too low

105

AC frequency too high

106

AC frequency too low

107

AC grid outside the permissible
limits

108

Stand alone operation detect-
ed