Fronius Agilo 360.0-3 TL User Manual

Page 72

Advertising
background image

70

Class 3 status
codes

Class 3 includes status codes that may occur while feeding energy into the grid, but gen-
erally do not cause the process to be interrupted for any length of time.

The inverter disconnects automatically from the grid, the grid is then monitored as specified
and the inverter attempts to resume feeding energy into the grid.

Class 4 status
codes

Some of the class 4 status codes necessitate intervention by a Fronius-trained service en-
gineer.

Code

Description

Behaviour

Remedy

301

Overcurrent (AC)

Short-term interruption while
feeding energy into the grid
due to overcurrent in the invert-
er
The inverter resumes with its
start-up routine.

Fault is rectified automatically;
If this status code keeps recur-
ring: notify a Fronius-trained
service engineer

303

Power stage set overtempera-
ture

Short-term interruption while
feeding energy into the grid
due to overtemperature
The inverter resumes with its
startup routine.

Purge cooling air openings and
heat sink if necessary;
fault is rectified automatically;
If this status code keeps recur-
ring, contact your system engi-
neer

304

Internal temperature too high

305

If the grid relay is closed, no
energy is transferred to the grid

Permanent interruption while
feeding energy into the grid

If this status code keeps recur-
ring, contact your system engi-
neer

307

DC low
DC input voltage too low for
feeding energy into the grid

Short-term interruption while
feeding energy into the grid
The inverter resumes with its
startup routine.

Fault is rectified automatically;
If this status code occurs when
there is sufficient insolation,
contact your system engineer

IMPORTANT! Due to the low level of insolation early in the morning and in the evening, the status code 307 (DC
low) is routinely displayed at these times of day. This status code does not indicate any kind of fault.

309

DC input voltage too high

Short-term interruption while
feeding energy into the grid
The inverter resumes with its
startup routine.

Fault is rectified automatically;
If this status code keeps recur-
ring, contact your system engi-
neer

321

Overcurrent (AC)

322

Overtemperature on the air in-
let sensor

Permanent interruption while
feeding energy into the grid

Reduce the ambient tempera-
ture and ensure that a suitable
hot air extractor is installed if
necessary
If this status code keeps recur-
ring, contact your system engi-
neer