Model 495-001 Mine Dial/Page Phone Interface Cabinet

Page: 8 of 22

f:\standard ioms - current release\42004 instr. manuals\42004-198d.doc
10/11

Connecting AC Power to the Rack

The Model 495-001 requires a 15-amp, single phase, 60 Hz, 120 V ac power source. The cable should be
routed through the underside of the 19-inch rack assembly and connected to the duplex outlet in the
bottom rear of the rack. Use an appropriate cable clamp (Romex, BX, etc.) for installation.

Connect the white wire from the power cable to the orange/black wire on the outlet. The black wire from
the power cable should connect to the red wire on the outlet. All ac circuits within the rack are pre-wired
to this outlet.

CAUTION

Be sure the AC

ON switch on the front panel is of the Power

Supply/Metering/ Panel assembly is in the down (Off) position before applying ac power.

Using Voltage Other than 120 V AC

N

OTE

: As an alternative, the Model 495-001 Interface Cabinet’s power supply can be wired for other

input voltages, including a 240 V ac input. Refer to Table 1 and Figure 6.

CAUTION

Disconnect all power from the unit before changing input voltage. Be sure to

change the primary fuse from 2 A for 120 V ac input to 1 A for 240 V ac input.

Table 1. Input AC Connections (See Case C Diagram)

For use at:

Connect:

Apply ac to:

Primary fuse:

100 V ac

1–3, 2–4

1 and 5

2.0 amp/ 125 V

120 V ac

1–3, 2–4

1 and 4

2.0 amp/ 125 V

220 V ac

2–3

1 and 5

1 amp/ 250 V

230 V ac

2–3

1 and 4

1 amp/ 250 V

240 V ac

2–3

1 and 4

1 amp/ 250 V

N

OTE

: Connect sense leads –S to –Out and +S to +Out.

Figure 6. Case C