GAI-Tronics 12599-002 Hot Standby Amplifier Module User Manual

Page 14

Advertising
background image

Pub. 42004-412A

Model 12599-002 Hot Standby Amplifier Module

Page: 14 of 17

\\s_eng\gtcproddocs\standard ioms - current release\42004 instr. manuals\42004-412a.doc
06/08

While it is difficult to determine which area of a facility is the most critical (as in item 2 above), an
example would be an offshore oil platform system with multiple amplifiers. In this case, the living
quarters (LQ) are usually considered such an area. In this type of system/cabinet design, the LQ amplifier
should be connected to the Amp-1 terminals to ensure that personnel (sleeping in the LQ) will be alerted
during emergencies.

Dry Contact Outputs

The Model 12599-002 Hot Standby Amplifier Module provides six, Form “C” dry contact outputs (one
per amplifier circuit) that can be used for triggering either a remote status indicator, or an input at a
supervised system device for visual text display. Each output contact operates in conjunction with its
respective fault detection circuit so that the status of all connected amplifiers can be monitored at all
times, regardless of their priority assignment.

Cascading Modules

The Model 12599-002 Hot Standby Amplifier Module can be operated with a series of other modules in a
cascade. This feature is useful in cabinet/system applications when the following criteria must be met:

• A higher ratio of primary (active) amplifiers to a standby amplifier is needed, or
• In particular, when dual-channel amplifiers are employed.

When using the cascade feature, the

IN/OUT

control at TB26 must be used between modules. For the

cascade to function properly, connect the

OUT

terminal of the first module to the IN terminal at the

second module. Do not make any connections to the IN

terminal at the first module. For subsequent

modules in the cascade, this in/out wiring arrangement must continue across all modules.

In addition to in/out control across modules, the mode switches S1 through S5 must also be set to the
proper operating position. See the Mode Switches (S1–S5) section below for information on the function
and settings of these switches.

Mode Switches (S1–S5)

The Model 12599-002 Hot Standby Amplifier Module is equipped with five mode control switches. The
function of each is switch is described below:

S1 Brd Cntl (Board control) – Since relay switching on this module is prioritized, this switch determines
if the module is operated as standalone, the first of multiple modules, or is operating behind another
module. If the module is used standalone, or is the first of multiple modules, the switch must be set to the
1

ST

position. However, if the module operates behind another module in a cascaded control path, the

switch must be set to the

2

ND

+ position.

S2/S3 Sw’g Cntl (Switching control) – Since this module is designed to switch either six single-channel
amplifiers or three dual-channel amplifiers, these two switches must be set to the appropriate position for
the type of amplifier being switched, e.g.,

1CH

(1-channel) or

2CH

(2-channel) respectively. (See the

note below.)

When the switches are set to the

1CH

position, all six relay circuit groups operate independently via

control from their respective fault input circuits. When the switches are set to the 2CH

position, the

Amp-1/Amp-4 circuits, Amp-2/Amp-5 circuits, and Amp-3/Amp-6 circuits are linked for switching both
channels of the amplifier simultaneously.

Advertising