Mode 2: idc single normally-open (n.o.) switch – GAI-Tronics 379-002 Monitored RElay Module (MRM) Stations User Manual

Page 7

Advertising
background image

Pub. 42004-491A

Model 379-002 Monitored Relay Module Station

Page 7 of 13

f:\standard ioms - current release\42004 instr. manuals\42004-491a.doc
03/14

Mode 2: IDC Single Normally-Open (N.O.) Switch

In this configuration, only one normally-open dry contact closure may be installed per supervised line. In
this mode, the loop is monitored for open circuits, wire-to-wire short circuits (across + and −), and ground
faults. When the contact closure is not active (open), the loop appears as 20.1 k

 load (15 k in series

with 5.1 k

). This appears on the input to the MIM and indicates a healthy loop. When the contact

closure is active (closed), the 15 k

 resistor is bypassed.

Figure 5. IDC Single Normally-Open Switch

When the contact closure is active (closed), the 15 k

 resistor is bypassed. In this case, output #1 only

sees a 5.1 k

 load. When this occurs, it indicates to the MRM that the contact closure is active. If there

is a short across L1 and L2, if either leg is grounded, or if a break occurs on either leg, the MRM indicates
that a fault has occurred.

N

OTE

: The terminating resistors are not included with the MRM. These resistors are included in a kit

(12509-004), which must be ordered separately.