Fault Message

Cause and Effect

Possible Solution

Polled End-of-line
device

Cause—This message is the same as the
“Polled device” fault, except that the affected
station has been defined as an end-of-line
station in the MCU configuration.

Effect—When this fault occurs, the red EOL

FLT LED on the PPI bezel lights. When
communication is resumed, the LED
extinguishes and a restore message is sent to the
MCU.

 Verify that the page line

is connected and intact.

 Verify that the station is

installed correctly.

 Replace the station

assembly.

Specifications

Electrical

Supply voltage .......................................................................... 90–140 V ac (120 V ac nominal), 50/60 Hz

Power consumed @ nominal ac ........... Zero/maximum signal (12 watts): 15 VA, 9 watts/59 VA, 32 watts

Speaker Amplifier

Output ............................................................................... 12 watts minimum, with nominal supply voltage

Frequency response .......................................................................... 350–6,500 Hz, +0/−3 dB, ref. to 1 kHz

Distortion ......................................................................................... 1% maximum THD @ 1 kHz, 12 watts

SmartVolume™

Monitor range (low gain) ...................................................................................................... 62–100 dB SPL

Offset (above ambient) user level adjustment ................................................................................... 0–48 dB

Minimum user level adjustment .................................................................................... Off; 85–125 dB SPL

Mechanical

Dimensions ....................................... 8.12 H

 8.12 W  3.12 D inches (206.0  206.0  78.7 mm) overall

Package weight ..................................................................................................................... 6.1 lbs. (2.8 kg)

Net weight ............................................................................................................................. 5.1 lbs. (2.3 kg)

Environmental

Temperature range ......................................... −22° F to +158° F (−30° C to +70° C) operating and storage

Humidity ..................................................................................................................... 95%, non-condensing

Approvals

NRTL Listed USA and Canada .............................................................. Class I, Div. 2, Groups A, B, C, D

when used with a listed GAI-Tronics 702 or 703 Series enclosure

Class I, Div. 2, Groups A, B, C, D;

Class II, Div. 2, Groups F, G; Class III, Div. 2

when used with a listed GAI-Tronics 732, 733, 7325, 7335, or 758 Series enclosure

Temperature code ....................................................................................................................................... T4