Operation, How to diagnose assembly/model faults – GAI-Tronics 12578-003 Monitored Input Module (MIM) User Manual

Page 10

Advertising
background image

Pub. 42004-715L2C

Model 12578-003 Monitored Input Module (MIM)

Page 10 of 12

f:\standard ioms - current release\42004 instr. manuals\42004-715l2c.doc
06/12

Operation

The operation of the Model 12578-003 MIM is controlled by the MCU configuration. See the MCU
configuration details in the system manual for all operation information.

How to Diagnose Assembly/Model Faults

Symptom Action

MIM does not
communicate
with MCU

 Verify power is applied to the MIM.
 Verify page line is connected to the MIM.
 Verify address of MIM agrees with the setup configuration.
 Ensure CPU PCBA is correctly connected via J1.
 Call for service of the MIM.

MIM does not
recognize dry
inputs

 Verify total loop resistance is less than 100 .
 Verify power is applied to the MIM.
 Verify page line is connected to the MIM.
 Verify end of line resistor(s) properly installed on each input circuit.
 Call for service of the MIM.

MIM does not
activate an
alarm with 24 V
dc applied to
input terminal.
(Wet contact
mode ONLY.)

 Verify that the jumper that selects the proper “_ V dc when active” mode is in

the correct position for the desired mode. Refer to Mode 5 - IDC Non-
Supervision (Wet Contact) information.

 Verify that the applicable input jumpers have been repositioned for WET

operation.

 Verify that the input is within the acceptable dc voltage range (20–30 V dc)
 Verify that the proper voltage polarity has been observed for external

connections to the input terminals.

 Call for service of the MIM.

Advertising