Installation guidelines, Mounting, Power – GAI-Tronics 12578-003 Monitored Input Module (MIM) User Manual

Page 4: Data communication line

Advertising
background image

Pub. 42004-715L2C

Model 12578-003 Monitored Input Module (MIM)

Page 4 of 12

f:\standard ioms - current release\42004 instr. manuals\42004-715l2c.doc
06/12

Installation Guidelines

1. Notify plant personnel of a system shutdown prior to servicing the unit.

2. Disconnect power before installing or removing the MIM.

Mounting

To install the module into the Snaptrack slide either the right or the left edge of the module into the top
groove on the track. On the opposite side, press firmly on the top and bottom corners of the module until
they snap into the groove. Carefully press from each corner toward the center and simultaneously snap
the edge firmly into place.

Power

After the PCBA is installed onto the Snaptrack, 12 V dc power is brought in from the auxiliary power
supply and terminated on TB9 (PWR IN). The positive leg is connected to TB9-1 (+) and the return leg is
landed on TB9-2 (−). An earth ground is connected to TB9-3 (EGND). TB9 is paralleled with TB10.
TB10 (PWR OUT) may be used to distribute power to additional Snaptrack modules.

N

OTES

:

 Although power may be daisy-chained between MIMs and other Snaptrack modules, the preferred

method of delivering power to these modules is by providing a dedicated cable run between each
module and the auxiliary power supply.

 The auxiliary power supply return leg must be connected to earth ground for proper operation. The

physical connection should be made at the auxiliary power supply terminals.

 The ground reference for this assembly must be identical to that of the enclosure.
 The MIM does not contain any current-limiting for power. It is recommended that an external fuse be

provided with the appropriate voltage and current ratings. The selected fuse should be of the slo-blo
variety.

Data Communication Line

Terminal blocks TB11 and TB12 are for the page line connection (FSK data communication) from the
PPI card and to additional MIM and MRM modules.

N

OTE

: The conductor terminated on TB12

should be a twisted pair.

FSK Signal Gain

The FSK Signal Gain, R8, adjusts the FSK transmit signal strength. It is set at the factory and should not
be adjusted by the installer.

Advertising