Specifications – GAI-Tronics 12578-003 Monitored Input Module (MIM) User Manual

Page 11

Advertising
background image

Pub. 42004-715L2C

Model 12578-003 Monitored Input Module (MIM)

Page 11 of 12

f:\standard ioms - current release\42004 instr. manuals\42004-715l2c.doc
06/12

Specifications

Electrical
Power requirements ........................................................................................ 9–15 V dc (12 V dc nominal)
Current draw .................................................................... 300 mA maximum @ 12 V dc (no ground faults)
Number of input loops ................................................................................................................. Eight loops
Maximum devices on input loop ..................................................................................... Unlimited (Mode 1)

One (Mode 2)

One (Mode 3)

Unlimited (Mode 5 – Dry)

One (Mode 5 – Wet)

Input/output ....................................................................................................................................... Power in

Power out

Page line (FSK) in

Page line (FSK) out

Eight field inputs

Data communications ............................................................................................................................... FSK
End-of-line device ................................................................................................................ 20 k

 (Mode 1)

5.1

k

 in series with 15 k across contact (Mode 2)

5.1

k

 in series with 15 k across contact (Mode 3)

None (Mode 5)

Field Inputs

Mode 1:
Contact closure resistance (activated) ................................................................................... 1 k

 maximum

Open fault detection ............................................................................................................ Minimum 65 k

Ground fault detection ......................................................................................... Less than 200

 to ground

Modes 2 and 3:
Contact closure resistance (Mode 2: activated/ Mode 3: de-activated) ................................ 3 k

 maximum

Open fault detection ............................................................................................................ Minimum 65 k

Ground fault detection ......................................................................................... Less than 200

 to ground

Wire-to-wire short fault detection ........................................................................................ Less than 200

Mode 5 (Dry)
Contact closure resistance ................................................................................................... 900

 maximum

Mode 5 (Wet)
DC input voltage range ................................................................................. 20–30 V dc (24 V dc nominal)

Limitations:
Cable limitations ........................................................................................ 100

 maximum loop resistance

Terminals:
Minimum conductor size ......................................................................................... No. 28 AWG (0.5 mm

2

)

Maximum conductor size ......................................................................................... No. 12 AWG (3.0 mm

2

)