Removal, 5 removal – Geist Upgradeable PDU User Manual

Page 22

Advertising
background image

Upgradeable PDU Instruction Manual

22

© 2015 Geist

GM1157 - GU PDU Instruction Manual

Once you have created the Admin account and logged into it, the unit's default
Sensors page should come up by default. Navigate to the System tab, then the
Network page to configure the device's network properties. The unit's IP Address,
Subnet Mask, Gateway, and DNS settings can either be assigned manually, or
acquired via DHCP.

Note that the new settings will take effect instantly when the Save button is clicked, so
the browser will no longer be able to reload the web page from the 192.168.123.123
address and will probably display a "page not found" or "host unavailable" message.
This behavior is normal. Once you have finished configuring the unit's IP address,
simply repeat the steps above, and change the computer's Ethernet NIC card settings
back to the ones you wrote down prior to changing them, to restore its normal
network and internet settings.

3.5

Removal

The IMD is designed to be field replaceable by qualified service personnel only.
The IMD module is hot-swappable, meaning it is designed to be replaced while the
PDU is still connected to AC power. If the Geist Upgradable PDU is going to be
upgraded by replacing the IMD module, follow the procedure described here:

Note: Be sure to have the new IMD module ready for installation immediately after
removal of the old IMD.

Advertising