Greenheck 331-4551, 332-4551 - Siemens 3 Actuator (454201) User Manual

Installation instructions, Caution, Warning

Advertising
background image

Part No. Quantity Description

1

1

Actuator Siemens #3

2

1

Swivel (assembled to actuator)

3

1

Post (assembled to actuator)

4

1

Clevis (assembled to actuator)

5

2

3

/

8

in

.-24 Hex Nut (assembled to actuator)

6

1

1

/

2 in.

Crankarm

7

1

5

/

16 in.

-18 x 1

1

/

2 in.

Bolt

8

1

5

/

16 in.

-18 Spinlock Nut

9

1

1

/

4 in.

x

1

/

2 in.

Clevis Pin

10

1

Hitchpin Cotter

These instructions apply to the external field installation of Siemens actuators on Greenheck models VCD Control Dampers
when they are duct mounted or sleeved.

This Siemens pneumatic actuator has an 8 square inch effective diaphragm area and a 2

3

/

4

in. stroke. It extends to its holding

position when air pressure is applied and spring returns to its fail position when the air supply is interrupted. This model has
a maximum air pressure of 25 psi.

Tools Required:

Wrenches:

(1)

3

/

8

, (2)

1

/

2

, and (1)

7

/

16

in.

Alt.

Alt.

Alt.

1

2

5

1.938

8

6

7

18

19

20

Cont

rol Shaf

t

To Damper

16

15

3

17

14

12

11

13

9

10

4

1.750

1 in. (25mm) Dia. Jackshaft Hardware
Replaces Item 6, 7, & 8
(supplied with damper)

Part No. Quantity Description
11

4

1

/

4

-20 x

1

/

2 in.

Bolt

12

4

1

/

4

-20 Spinlock Nut

13

1

Mounting Bracket

14

1

Ball Bearing

15

1

Stand Off Bracket

16

4

1

/

4

-20 x

1

/

2 in.

Self Threading Screw

17

2

#10 TEK Screw

18

1

3

/

8

-16 x 2

1

/

2 in.

Carriage Bolt

19

1

1 in. Crankarm (Knurled)

20

1

3

/

8

-16 Spinlock Nut ZP

Part Number 454201

Siemens #3 Actuator

Model 331-4551 & 332-4551

UL Listed Pneumatic Actuator with Spring Return

INSTALLATIoN INSTRUcTIoNS

!

!

cAUTIoN

Device Malfunction Hazard. Improper set screw tightening causes device malfunction. Tighten set screws with
proper torque to prevent damper shaft slippage.

!

!

WARNING

Equipment Damage or Electrical Power Hazard. Line voltage can cause death or serious injury and short equipment
circuitry. Disconnect power supply before installation.