Installation Instructions for

Close Indicator Switch

“UL CLASSIFIED
(see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standards

UL555

Classifications filed at UL under Listing #R13317

Refer to:
‘Installation Instructions for FD, DFD, SSFD Models Fire’
(Part #452763)

‘Installation Instructions for FD & DFD 150X Series
Curtain Fire Damper’ (Part #453946)

Installation Instructions:

1. Position the switch near the center of the frame

bottom. The switch bracket should be positioned
against the frame rib. Transfer the two bracket
mounting holes to the frame. Using a .281dia. drill
bit, drill the two holes through the damper frame.

2. Remove the switch cover and attach the electrical

wires to the appropriate terminals of the switch.
Reassemble the cover to the switch. Make sure
the wires do not short each other. Tighten the

screws that hold the switch and cover to the
bracket.

3. Attach the switch bracket to the frame using

the supplied screws and nuts. Make sure the
switch bracket is pushed against the frame rib,
then tighten the fasteners. Cycle the switch lever
to make sure that it clears the frame ribs and
operates freely. If interference detected, bend the
switch lever or reposition the moutning bracket.

© Copyright 2010 Greenheck Fan Corporation

474050 Close Indicator Switch Rev. 1 July 2010

®