Checks

If any discrepancies or malfunctions are noted during the inspections,
NORTEC Customer Service should be notified immediately! Only trained personnel
should perform inspections. The Operator is responsible for ensuring that the
personnel is qualified and properly trained.






Infeed

Product












Filter 20µ

Figure 17: installation rail


SynPur:

Inspection of the product: Extract 3L of product from the
sampling tap (6) and check the quality of the product with a
calibrated conductivity tester. It is important to use a clean
bucket to make no measuring mistakes. The value has to be
in the range 7

– 22 micro Siemens. If the measured value is

out of the range, please contact the NORTEC service
department.

Cycle:

Every 2 weeks


Synthesizer cartridge:


Inspection of the DM water: Extract 3L of DM water from
the sampling tap (5) and check the quality of the water with a
calibrated conductivity tester. It is important to use a clean
bucket to make no measuring mistakes. The value has to be
in the range 0

– 1 micro Siemens. If the measured value is out

of the range, it could be the synthesizer cartridge has to be
exchanged.

Cycle:

Every 2 weeks



Filter (4):

For each regular servicing of the SynPur the filter of the
installation rail must be replaced. These are delivered with the
exchange container.