Maintenance, Seasonal maintenance, Seasonal startup – Nortec AIRFOG Series User Manual

Page 35

Advertising
background image

AirFog Installation Manual | 31

Maintenance

The two most probable maintenance problems are:
 The accumulation of dirt and mineral deposits in/on the nozzle
 Air and water leaks that may be due to marginal workmanship during installation but not

obvious until after many hours of operations.

Nozzle cleaning is recommended at least once a year. Remove the nose cone from the nozzle

body by turning it by hand and mechanically remove deposits by gentle scraping or scrubbing
with a brush or steel wool. Care must be taken not to damage the nozzle or its surfaces. Wipe
clean using a clean dry rag.
Leaks in the air and water delivery system could develop over time as the mechanical seals age.

Full nozzle replacement, taken from the spare parts purchased as part of initial acquisition, is
the recommended maintenance procedure if a nozzle should cease to perform. The nozzle can
be repaired back at the workshop using a Level III maintenance nozzle repair kit. Leaks in the
piping can be repaired using standard plumbing methods.
Repair kits for the AFE nozzle, Vacuum Valve, Air Regulator and the Water Regulator are
available. Instructions are provided with each kit.

Seasonal Maintenance

In most cases there is a humidification season but if this is not the case, it is recommended that
the following actions be conducted once a year.
 A detailed visual leak inspection using soapy water and low pressure (less that 10 psig) of all

air and water transport pipes and system components is to be recorded on a sketch to
indicate leak locations and severity.

 Comparison with previous inspection records could indicate systematic problems as

compared to random events.

 Repair leaks and verify the system is fully operational using the procedure described in the

Start Up section of this guide.

 The AirFog system is to be shutdown in accordance with the procedure described in the Shut

Down section of this guide.

 Each nozzle shall be cleaned of mineral water deposits and accumulated dirt using the

procedure described in the Maintenance section of this guide.

 Each nozzle should be lubricated using a silicone based lubricant.
 The compressor manual should be consulted for its recommended seasonal maintenance.

Seasonal Startup

A detailed visual inspection of all air and water transport pipes and components is to be

recorded on a humidification system sketch to indicate damage, non-conformances and
abnormalities.
Comparison with previous inspection records could indicate systematic problems as compared

Advertising