AirFog Installation Manual | 5

Installation

Nozzle System Layout

If a drawing for the proposed system was not supplied, then it is recommended that one be
created prior to installing the system. With reference to the AirFog Engineering Manual, review
the site where the nozzle system is to be installed. The location of equipment, lights, pillars and

other structures should be drawn on the floor plans. The proper selection and location of the
nozzles is very dependent upon these obstructions. Figure 1: Typical Nozzle Layout, can be
used as a guide for identifying the various components used with a system.
The supply and feed lines for the system should be kept in straight unobstructed lines where

possible. Air and water distribution network pipes are to be installed level along walls, pillars or
hung from the ceiling. Avoid placing the lines over top of equipment and other areas, which will
make it difficult to gain access at a later date. If the lines have to be routed around an obstacle
such as a beam, always go under the obstacle, never over it.


Figure 1: Typical Nozzle Layout for Wall Mounted System