Nortec LINKS 2 GSTC User Manual

Page 19

Advertising
background image

Installation

|

15

Table 4: Variable Definitions - CONTINUED

Variable Name

R=Read

W=Write

Description

LonWorks SNVT

nvoSet1_x

R

Analog Value

Reads setpoint for relative humidity
in space. (0%-100%).

SNVT_lev_percent

nvoRHDem2_x

R

Analog Value

Reads duct %RH or secondary
space %RH, or secondary
%demand to humidifier. (0%-100%)
Choice determined by
nviInputType_x.
Dip Switch 4/5 on humidifier’s logic
board must be ON

SNVT_lev_percent

nvoDisable_x

R

Binary Value

Reads remote disable status.
0=humidifier enabled, 1=humidifier
disabled by network

SNVT_switch

nvoService_x

R

Binary Value

Reads service requirement status.
0=no service required, 1=service
required

SNVT_switch

nvoStatus_x

R

Binary Value

Reads humidifier status. 0=standby,
1=humidifying

SNVT_switch

nvoConnection_x

R

Binary Value

Indicates that the Nortec Links
module is communicating with the
humidifier

SNVT_switch

nvoKeepWarm_x

R

Binary Value

Indicates that the KeepWarm feature
has been enabled

SNVT_switch

nvo3DayDrain_x

R

Binary Value

Indicates that the 3 day drain feature
has been enabled

SNVT_switch

nviDisable_x

W

Binary Value

Writes remote disable status.
0=humidifier enabled, 1=humidifier
disabled from network

SNVT_switch

nviInputType_x

W

Binary Value

Writes the input type status.
0=unit accepts a %demand signal
1=unit accepts on/off signal

SNVT_switch

nviNetSensor _x

W

Binary Value

Writes configuration status for
network-enabled sensing or control.
0=%RH or %demand input is not
from the network
1=%RH or %demand input is from
the network

SNVT_switch

Advertising
This manual is related to the following products: