Nortec LINKS 2 GSTC User Manual

Page 23

Advertising
background image

Installation

|

19

Table 8: Humidifier Variable Addresses - Unit #4

Unit #4

BACnet

Lonworks

N2

Variable Name

Type

Instance

SNVT

SNVT # NV Index Element Type Instance

nvoHourOpt_4

AV

43

SNVT_time_hour

124

70

1

AI

43

nvoRHDem1_4

AV

44

SNVT_lev_percent

81

71

1

AI

44

nvoSet1_4

AV

45

SNVT_lev_percent

81

72

1

AI

45

nvoRHDem2_4

AV

46

SNVT_lev_percent

81

73

1

AI

46

nvoSet2_4

AV

47

SNVT_lev_percent

81

74

1

AI

47

nvoSysDemand_4

AV

48

SNVT_lev_percent

81

75

1

AI

48

nvoServHours_4

AV

49

SNVT_time_hour

124

76

1

AI

49

nviRHDem1_4

AV

50

SNVT_lev_percent

81

77

1

AO

50

nviRHDem2_4

AV

51

SNVT_lev_percent

81

78

1

AO

51

nviSet1_4

AV

52

SNVT_lev_percent

81

79

1

AO

52

nviSet2_4

AV

53

SNVT_lev_percent

81

80

1

AO

53

Analog Expansion_4

AV

54

N/A

N/A

N/A

N/A

N/A

N/A

Analog Expansion_4

AV

55

N/A

N/A

N/A

N/A

N/A

N/A

nviDisable_4

AV

56

SNVT_switch

95

89

N/A

AO

56

nvoInputType_4

BV

43

SNVT_switch

95

81

2

BI

43

nvoFault_4

BV

44

SNVT_switch

95

82

2

BI

44

nvoNetSensor_4

BV

45

SNVT_switch

95

83

2

BI

45

nvoDisable_4

BV

46

SNVT_switch

95

84

2

BI

46

nvoService_4

BV

47

SNVT_switch

95

85

2

BI

47

nvoStatus_4

BV

48

SNVT_switch

95

86

2

BI

48

nvoKeepWarm_4

BV

49

SNVT_switch

95

87

2

BI

49

nvo3DayDrain__4

BV

50

SNVT_switch

95

88

2

BI

50

Expansion1_4

BV

51

N/A

N/A

N/A

N/A

N/A

N/A

nviInputType_4

BV

52

SNVT_switch

95

90

2

BO

52

nviNetSensor_4

BV

53

SNVT_switch

95

91

2

BO

53

nvoConnection

BV

54

SNVT_switch

95

92

2

BO

54

Expansion2_4

BV

55

N/A

N/A

N/A

N/A

N/A

N/A

Expansion3_4

BV

56

N/A

N/A

N/A

N/A

N/A

N/A