Step 2 – wiring the nortec links 2 module – Nortec LINKS 2 SETC B+ User Manual

Page 9

Advertising
background image

5 | Links 2 Retrofit for GSTC / SETC B+, NHTC, NHRS

Step 2 – Wiring the Nortec Links 2 Module

1 Most of the wiring connections for the new Nortec LINKS 2 module will have already been

finished at the factory; however, there are a few connections that will need to be made to
connect the unit the GS/SE series humidifier. Refer the LINKs 2 wiring diagram included in
the package for details.

2 Module Power Connections: There will be a wire harness provided that will consist of a red

and blue wire. Both red and blue wires are terminated with a ring terminal.
a The ring terminal of the red wire is to be connected to the power terminal on the 24V

side of the transformer located at the bottom, left of the electrical compartment.

b The ring terminal of the blue wire is to be connected to the ground terminal on the 24V

side of the transformer.

3 Humidifier Communication Connection: On the Nortec LINKS 2 assembly there will be a

CAT5 cable with RJ45 connector.
a This connector is to be plugged into the jack on the bottom right side of the humidifier

main PCB board.

Figure 6: Component Identification

LAN Router or
Switch
(BACnet/IP)

OnLine

Module

LINKS 2

Module

Router

Power

Supply

CAT5

cable

Red and blue
wires