Control signal setting – Nortec BACnet User Manual

Page 13

Advertising
background image

9 | BACnet & LONWORKS Supplemental Install Manual

Control Signal Setting

By default the humidifier is configured to operate on a hardwired control signal supplied through
the unit terminal strip. This can be changed to allow the humidifier to function entirely through
its BACnet interface.
*Note: the Humidifier Security loop will still need to be enabled for humidifier to run.

To adjust this setting:

1 Press the Menu icon on the lower left corner of the status screen, to access the menu.
2 When prompted for a password, enter 0335 using the number pad. Press the Check Mark

icon to confirm.

3 Select the Configuration menu.
4 Select the Control Settings menu. The following settings can be adjusted:

Table 4: Control Signal Parameters

Source

Analog: Use hardwired control signal
BACnet/IP:
Write control signal through BACnet/IP interface
BACnet/MS:
Write control signal through BACnet/MS interface

Control Mode

Demand: Use a demand control signal
RH P: Use a sensor value and proportional
RH PI: Use a sensor value and proportional-integral control band

Control Channels

Single: Use a single channel control signal
Dual: Use a dual channel control signal

Note: Refer to the CONTROL SETTING section of the NH-EL Installation and Operation Manual
for more information on the above settings.

5 Press Back repeatedly to return to the home screen when complete.

This procedure is summarized below:
Main Menu > 0335 > Configuration > Control Settings >

Source: Analog, BACnet/IP, BACnet/MS,
Control Mode: Demand, RH P, or RH PI
Control Channels: Single or Dual

Advertising
This manual is related to the following products: