Nortec BACnet User Manual

Page 29

Advertising
background image

25 | BACnet & LONWORKS Supplemental Install Manual

Table 12: Common Settings – Baud rate BTL BACnet MS/TP

Setting

B4

B3

B2

B1

Auto*

Off

Off

Off

Off

110

Off

Off

Off

On

300

Off

Off

On

Off

600

Off

Off

On

On

1200

Off

On

Off

Off

2400

Off

On

Off

On

4800

Off

On

On

Off

9600

Off

On

On

On

19200

On

Off

Off

Off

20833

On

Off

Off

On

28800

On

Off

On

Off

38400

On

Off

On

On

57600

On

On

Off

Off

76800

On

On

Off

On

115200

On

On

On

Off

* Auto baud is only supported for BACnet MSTP